Dual Phase Cut Module 30VA per channel – IOPC2
£76.00 Exc. VAT
The IOPC2 converts two 0-10V dc Input Signals to drive two separate 0-20V 50Hz phase-cut outputs, at 30VA per channel for the control of small valve or damper actuators.
Description
The IOPC2 converts two 0-10V dc Input Signals to drive two separate 0-20V 50Hz phase-cut outputs, at 30VA per channel for the control of small valve or damper actuators. The IOPC2 features optoisolator is powered from 24V ac (with a common connection to the input signal), and has Rising Clamp Screw Terminals. The output from the IOPC2 can be boosted to 60VA by using two IOPCA1, 1 per channel.
Specification
Input Signal: 2 x 0 – 10Vdc
Output Signal: 2 x 20V phase cut – 30VA per channel.
Power Supply: 24Vac (common to 0 – 10Vdc input).
Terminals: Rising clamp for 0.5 – 2.5mm² cable.
LED Indicators: ON when Power on.
Ambient Temp: 0 to 50˚C
Dimensions: 78 x 92.5 x 55mm (approx.)