Ultrasonic Flow / Heat Meter
£806.00 Exc. VAT
Fixed Non-invasive Flow Meter Assembly – A non-intrusive Flow meter and volume flow display enable quick and easy installation of clamp-on flow sensors, without the need to make contact with water and cut into existing pipe work.
Fixed Ultrasonic Flow Meter Assembly:: Clamp-on Sensors 50mm - 700mm
Fixed Non-invasive Flow Meter Assembly
Clamp-on Sensors 50mm - 700mm
Wall Mount Display: m3, Litres, Gallons etc
90-260V AC or 24V DC
Pulse, Alarm, 4-20mA Output, Modbus comms RTU or ASIC
A non-intrusive Flow meter and volume flow display enable quick and easy installation of clamp-on flow sensors, without the need to make contact with water and cut into existing pipe work.
Specifications:
The specifications for Fixed ultrasonic flowmeter | |
Measuring Principle | Ultrasonic wave transmission time difference principle, dual CPU working in parallel, 4-byte floating-point operations |
Accuracy | Better than ± 1.0 % |
Repeatability | 0.2% |
Velocity | 0.03-± 32 m/s |
Measurement Period | 0.5S |
Display | Backlit LCD can display 2x20 letters instantaneous flow, cumulative flow, velocity, time, calories, and other data signal output at the same time, etc. |
Keypad | 4x4-key membrane keypad with tactile feedback |
Input | Can input two current signals(such as temperature, pressure, liquid level, etc. signals ) in order to achieve heat measurements or a dual-purpose machine |
Output | Electric current signal 4-20mA or 0-20mA, etc. RS 485 Impedance 0 - 1K, accuracy 0.1% |
Isolated OCT output | For frequency output (0-9, 999Hz) |
Internal Alarm (Buzzer) | User programmable |
External Alarm Driver | The alarm signal can be transmitted to the Relay or OCT output terminals to drive an external alarm. |
Data Interface | RS-232 serial port or MODBUS RTU/ASIC |
Power | AC: 90V to 260V DC: 8~36VDC or AC7-30V |
Power Consumption | < 2W |
Work time | Continuous |
Environment Temperature | -30-80 Degrees Celsius |
Environment Humidity | 85% RH |
BFU-100-F Fixed Ultrasonic Flow Meter Assembly
Clamp-on Sensors 50mm - 700mm
Non-Intrusive design requires no servicing with zero wearable parts - Accurate Bi-directional flow measurement and logging.
Specifications:
Applications
• Water / Wastewater / Effluent
• Hot Water / Chilled Water / Mixture of Water and Glycol
• Petroleum Products
• Oil / Crude Oil / Fuel Oil / Diesel/ BioDiesel / Lubricant
• Oil /Hydraulic Oil (non-aerated)
• Chemical and Solvents
• Water management in buildings, Civil structures, District Heating/wastewater treatment plants, irrigation systems, and more
• Flow monitoring and flow control in Desalination plants, steel-making plants, power plants, machining plants
• Liquid process control in chemical plants and industrial automation application
• Retrofit capability, to upgrade or augment existing systems using this non-intrusive technology
• Automated batching
• Efficiency monitoring and improvement of heating/cooling systems, including solar/geothermal systems
• Hygienic Beverage, food, and pharmaceutical processing application

UartAssist - UartAssist serial debugging assistant V5.0.3 Software to check the Modbus communications from the heat meter.
Reviews